Appropriate, safe, weather-tight, pest-resistant, and effective termination fittings with unrestricted air flow
Specifications
- SF
- MH
- MF
Specification | Objective |
---|---|
Select termination fitting: that is appropriate for regional weather conditions and installation location with an integrated collar at least the same diameter as the exhaust duct outlet with an integrated pest screen with holes no less than 1/4" and no greater than 1/2", except for dryer terminations which will have no pest screen for kitchen exhaust: made from galvanized steel, stainless steel, or copper for dryer exhaust: that is designed for dryers exhaust and does not include a pest screen in very cold climates: that have no backflow dampers or use backflow dampers that resist freezing |
Appropriate, safe, and weather resistant termination |
- SF
- MH
- MF
Specification | Objective |
---|---|
Damper must open in the direction of the desired flow Damper will close when system is off No damper is required if the system operates continuously |
Prevent unwanted air movement while not restricting desired air flow |
- SF
- MH
- MF
Specification | Objective |
---|---|
Install termination to exhaust to the outdoors, which does not include unconditioned spaces such as attics and crawl spaces that are ventilated with the outdoors Install terminations: A minimum of 3' away from any property line; A minimum of 3' away from operable opening to houses; A minimum of 10' away from mechanical intake; Above the snow-line. If the termination is at the soffit, seal all soffit vents within 6' of the termination |
Prevent exhaust from reentering the structure |
- SF
- MH
- MF
Specification | Objective |
---|---|
Cut hole no larger than a 1/4" greater than the termination fitting Weather seal and flash the exterior fitting Mechanically fasten termination in place following manufacturer specifications Do not inhibit damper operation if included in termination |
Weather-resistant, durable, and effective installation |
- SF
- MH
- MF
Specification | Objective |
---|---|
If termination collar is larger than exhaust duct install a rigid metal transition |
Effective termination connection |
- SF
- MH
- MF
Specification | Objective |
---|---|
Seal all duct connections with UL 181B or 181B-M listed materials (e.g., mastic, tape) |
Airtight duct connections |