Durable, safe, airtight, and effective ventilation ducts that move the required air volume
Specifications
- SF
- MH
- MF
Specification | Objective |
---|---|
Select duct materials that have a flame spread no greater than 25 Select flexible ducts that are UL 181 listed or Air Diffusion Council approved Select rigid ducts of 28 gauge or thicker Select duct insulation with a flame spread/smoke development index of 25/50 or less when tested according to ASTM E84 or UL 723 |
Select durable, safe, and effective duct materials |
- SF
- MH
- MF
Specification | Objective |
---|---|
Install ventilation ducts as short, straight, smooth and fully extended as possible considering the following: Vent termination location; Amount of space for duct run; Roof condition, type, and access (e.g., metal, shingle, bowstring, flat) Choose duct diameter that is equal to or greater than the exhaust fan outlet Slope duct downwards towards the termination when possible Install flexible duct so the radius at the centerline of any turn is no less than one duct diameter |
Smooth and direct air movement |
- SF
- MH
- MF
Specification | Objective |
---|---|
If combining ducts, combine them on the upstream side of fan using "Y"-fittings or collection boxes Do not combine dryer, kitchen, or garage exhausts streams with any other exhaust stream |
Effective, safe exhaust of air from multiport systems |
- SF
- MH
- MF
Specification | Objective |
---|---|
Fasten all ducts as follows: Round metal-to-metal or metal-to-PVC with a minimum of three equally spaced screws For other metal-to-metal or metal-to-PVC with welds, gaskets, mastics (adhesives), mastic-embedded-fabric systems, or tapes Flexible duct-to-metal or flexible duct-to-PVC with tie bands using a tie band tensioning tool PVC-to-PVC materials with approved PVC primer and cement Fasten other specialized duct fittings in accordance with manufacturer specifications |
Durable duct connections |
- SF
- MH
- MF
Specification | Objective |
---|---|
Seal all duct connections with UL 181B or 181B-M listed materials (e.g., mastic, tape) |
Airtight duct connections |
- SF
- MH
- MF
Specification | Objective |
---|---|
Insulate all ducts installed outside of the thermal boundary to a minimum of R-8 Insulate all ductwork exposed to the exterior of the building to a minimum of R-12 |
Prevent condensation |
- SF
- MH
- MF
Specification | Objective |
---|---|
Support flexible and duct board ducts every 4' or less using a minimum of 1-1/2" wide material Install support materials in a way that does not crimp ductwork or cause the interior dimensions of the ductwork to be less than specified Support metal ducts every 10' or less using 1/2" or wider material, using 18 gauge or greater strapping or 12 gauge or greater galvanized wire |
Ducts secured to prevent damage |