Safe, balanced, and effective airflow control
Specifications
- SF
- MF
Specification | Objective |
---|---|
Verify: air flow regulator specifications are appropriate to site conditions(e.g., duct size, type, shape, register type, duct static pressure) presence and type of fire dampers and smoke control devices |
Verify safety and appropriate regulator design |
- SF
- MF
Specification | Objective |
---|---|
Select appropriate air flow regulator or orifice for the opening and desired airflow that will not interfere with the operation of smoke and fire dampers |
Moderate air flow safely and efficiently |
- SF
- MF
Specification | Objective |
---|---|
Securely fasten transition or adapter according to manufacturer specifications Install flow control device in the proper orientation for the desired flow direction Set adjustable devices to preliminary balancing position per the design specifications |
Secure and properly oriented device |
- SF
- MF
Specification | Objective |
---|---|
Seal all connections with UL 181B or 181B-M listed materials (e.g., mastic, tape) |
Airtight installation |
- SF
- MF
Specification | Objective |
---|---|
Verify installed air flow device will not interfere with proper operation of smoke and fire dampers |
Proper function of fire safety systems |