Efficient, safe, quiet, and effective removal of air contaminants from area
Specifications
- SF
- MH
- MF
Specification | Objective |
---|---|
Select a fan that: produces no more than 2.0 sones at maximum speed has an efficacy of 4 cfm/watt or more moves at least 50 cfm after installation, ducting, and termination is complete Select a fan that:
has an efficacy of 4 cfm/watt or more moves at least 50 cfm after installation, ducting, and termination is complete |
Select efficient and quiet equipment Select efficient and quiet equipment |
- SF
- MH
- MF
Specification | Objective |
---|---|
Select sealants that: are compatible with their intended surfaces, allow for differential expansion and contraction between dissimilar materials, meet the requirements of the applicable fire safety code (e.g., thermal or ignition barriers), and for use inside the pressure boundary select low volatile organic compound (VOC) sealants that meet independent testing and verification protocols |
Select safe and effective sealant |
- SF
- MH
- MF
Specification | Objective |
---|---|
If the fan does not contain an integrated damper, install a damper that: opens in the direction of the desired flow closes when the system is off If the fan does not contain an integrated damper, install a damper that: opens in the direction of the desired flow closes when the system is off fan housing connections shall not interfere with damper operation |
Prevent unwanted air movement while not restricting desired air flow Prevent unwanted air movement while not restricting desired air flow |
- SF
- MH
- MF
Specification | Objective |
---|---|
Install fan near the center of the space where odor, moisture, or other contaminants are generated but not inside a shower unless fan is rated for wet location installation |
Effective location for removal of contaminants |
- SF
- MH
- MF
Specification | Objective |
---|---|
Cut hole for fan leaving no more than a 1/4" gap on each side of the fan assembly |
Properly sized opening |
- SF
- MH
- MF
Specification | Objective |
---|---|
Orient the fan outlet toward the final termination location and so the equivalent length of the duct run is as short as possible |
Short, effective fan venting |
- SF
- MH
- MF
Specification | Objective |
---|---|
Mount fan using mechanical fasteners and per manufacturer's specifications so that fan housing does not shake, rattle, or vibrate when operating |
Securely mounted fan |
- SF
- MH
- MF
Specification | Objective |
---|---|
Install all electrical wiring according to manufacturer specifications and applicable code |
Prevent an electrical hazard |
- SF
- MH
- MF
Specification | Objective |
---|---|
Seal gap around fan housing and enclose fan housing when possible |
Airtight fan installation |
- SF
- MH
- MF
Specification | Objective |
---|---|
If fan housing is installed in unconditioned space, insulate fan housing to a minimum of R-8 or cover with insulation of more than R-8 |
Prevent condensation |
- SF
- MH
- MF
Specification | Objective |
---|---|
Ensure fan and service disconnect switch are accessible for maintenance according to NEC, or applicable building code |
Accessible for service |
- SF
- MH
- MF
Specification | Objective |
---|---|
Duct and terminate fan to the outdoors, which does not include unconditioned spaces such as attics and crawl spaces that are ventilated with the outdoors, in accordance with SWS detail for "Ventilation Ducts" |
Exhausted to outdoors |