Surface Mounted

Detail ID 6.0201.1
Topic
Local Ventilation
Subtopic
Exhaust Systems
Desired Outcome

Efficient, safe, quiet, and effective removal of air contaminants from area

SF Single Family Site-Built Housing
MH Manufactured Housing
MF Multifamily Housing

Specifications

  • SF
  • MH
  • MF
Specification Objective

Select a fan that:

produces no more than 2.0 sones at maximum speed

has an efficacy of 4 cfm/watt or more

moves at least 50 cfm after installation, ducting, and termination is complete

Select a fan that:

producesrated as no more than 2.0 sones at maximum speed

has an efficacy of 4 cfm/watt or more

moves at least 50 cfm after installation, ducting, and termination is complete

Select efficient and quiet equipment

Select efficient and quiet equipment

  • SF
  • MH
  • MF
Specification Objective

Select sealants that:

are compatible with their intended surfaces,

allow for differential expansion and contraction between dissimilar materials,

meet the requirements of the applicable fire safety code (e.g., thermal or ignition barriers), and

for use inside the pressure boundary select low volatile organic compound (VOC) sealants that meet independent testing and verification protocols

Select safe and effective sealant

  • SF
  • MH
  • MF
Specification Objective

If the fan does not contain an integrated damper, install a damper that:

opens in the direction of the desired flow

closes when the system is off

If the fan does not contain an integrated damper, install a damper that:

opens in the direction of the desired flow

closes when the system is off

fan housing connections shall not interfere with damper operation

Prevent unwanted air movement while not restricting desired air flow

Prevent unwanted air movement while not restricting desired air flow

  • SF
  • MH
  • MF
Specification Objective

Install fan near the center of the space where odor, moisture, or other contaminants are generated but not inside a shower unless fan is rated for wet location installation

Effective location for removal of contaminants

  • SF
  • MH
  • MF
Specification Objective

Cut hole for fan leaving no more than a 1/4" gap on each side of the fan assembly

Properly sized opening

  • SF
  • MH
  • MF
Specification Objective

Orient the fan outlet toward the final termination location and so the equivalent length of the duct run is as short as possible

Short, effective fan venting

  • SF
  • MH
  • MF
Specification Objective

Mount fan using mechanical fasteners and per manufacturer's specifications so that fan housing does not shake, rattle, or vibrate when operating

Securely mounted fan

  • SF
  • MH
  • MF
Specification Objective

Install all electrical wiring according to manufacturer specifications and applicable code

Prevent an electrical hazard

  • SF
  • MH
  • MF
Specification Objective

Seal gap around fan housing and enclose fan housing when possible

Airtight fan installation

  • SF
  • MH
  • MF
Specification Objective

If fan housing is installed in unconditioned space, insulate fan housing to a minimum of R-8 or cover with insulation of more than R-8

Prevent condensation

  • SF
  • MH
  • MF
Specification Objective

Ensure fan and service disconnect switch are accessible for maintenance according to NEC, or applicable building code

Accessible for service

  • SF
  • MH
  • MF
Specification Objective

Duct and terminate fan to the outdoors, which does not include unconditioned spaces such as attics and crawl spaces that are ventilated with the outdoors, in accordance with SWS detail for "Ventilation Ducts"

Exhausted to outdoors