Efficient, safe, quiet, and effective removal of air contaminants from kitchens
Specifications
- SF
- MH
- MF
Specification | Objective |
---|---|
Select a fan that: is rated a maximum of 3 sones at one or more airflow settings greater than or equal to 100 cfm has a minimum efficacy of 2.8 cfm/watt moves at least 100 cfm intermittently or 5 kitchen air changes per hour (ACH) continuously after installation, ducting, and termination is complete |
Select efficient and quiet equipment that moves the specified amount of air. |
- SF
- MH
- MF
Specification | Objective |
---|---|
Select sealants that: are compatible with their intended surfaces, allow for differential expansion and contraction between dissimilar materials, meet the requirements of the applicable fire safety code (e.g., thermal or ignition barriers), and for use inside the pressure boundary select low volatile organic compound (VOC) sealants that meet independent testing and verification protocols |
Select safe and effective sealant |
- SF
- MH
- MF
Specification | Objective |
---|---|
Install fan within at least 5' of the primary cooking surface (e.g., range, oven, stove) |
Effective location for removal of contaminants |
- SF
- MH
- MF
Specification | Objective |
---|---|
If the fan does not contain an integrated damper, install a damper that: opens in the direction of the desired flow closes when the system is off |
Prevent unwanted air movement while not restricting desired air flow |
- SF
- MH
- MF
Specification | Objective |
---|---|
Mount fan using mechanical fasteners and per manufacturer specifications so that fan housing does not shake, rattle, or vibrate when operating Ensure internal components are correctly oriented to exhaust air through the duct system |
Securely mounted and vent ready fan |
- SF
- MH
- MF
Specification | Objective |
---|---|
Install all electrical wiring according to manufacturer specifications and applicable code |
Prevent an electrical hazard |
- SF
- MH
- MF
Specification | Objective |
---|---|
Seal any gap around fan housing where air can leak to outside the pressure boundary |
Reduce infiltration |
- SF
- MH
- MF
Specification | Objective |
---|---|
Ensure fan and service disconnect switch are accessible for maintenance according to NEC, or applicable building code |
Accessible for service |
- SF
- MH
- MF
Specification | Objective |
---|---|
Duct fan flow through smooth wall metal duct and terminated to the outdoors, which does not include unconditioned spaces such as attics and crawl spaces that are ventilated with the outdoors, in accordance with SWS detail for "Ventilation Ducts" |
Safely exhausted to outdoors |
- SF
- MH
Specification | Objective |
---|---|
Provide make-up air if the range hood operation interferes with combustion appliance operation |
Prevent excessive depressurization from fan |
- MF
Specification | Objective |
---|---|
Provide make-up air if the range hood operation interferes with combustion appliance operation or if the fan exhausts more than 200 CFM |
Prevent excessive depressurization from fan |