Efficiently supply adequate, clean ventilation air
Specifications
- MF
Specification | Objective |
---|---|
Select a fan that: has an electrically commutated motor (ECM) and/or utilizes (VFD) controllers is capable of maintaining a minimum operating static pressure of .25 inches of water column or greater motors 1 horsepower or larger must meet NEMA premium efficiency standards motors less than 1 HP must be rated by the Home Ventilation Institute to satisfy these requirements |
Adequate and efficient fan motor |
- MF
Specification | Objective |
---|---|
Install intake to pull air from the outdoors, which does not include unconditioned spaces such as attics and crawl spaces that are ventilated with the outdoors Install intake: A minimum of 6" from grade; A minimum of 10' from contaminant sources or exhaust outlets; Above local snow or flood line; A minimum of 18" above an asphalt based roof; Never on a flat roof |
Unrestricted entry of contaminant-free air |
- MF
Specification | Objective |
---|---|
Label exterior intake fitting with the words "Ventilation Air Intake" |
Prevent fitting restriction |
- MF
Specification | Objective |
---|---|
Install corrosion resistant screen, louver, or grille material over exterior intake with a hole size of no less than 1/4" and no greater than 1/2" in any direction |
Prevent pest entry while allowing proper air flow. |
- MF
Specification | Objective |
---|---|
Install a motorized damper or equivalent between the intake fitting and the return side duct connection Damper will be open only when the air handler fan is operating |
Prevent unwanted air flow |
- MF
Specification | Objective |
---|---|
Design one or more supply fans located upstream of all the supply outlets to run continuously, or install a system of one or more backdraft dampers to isolate each dwelling unit from the common duct when the fan is not running. |
Prevent air movement between dwelling units |
- MF
Specification | Objective |
---|---|
Install all electrical wiring according to manufacturer specifications and applicable code |
Prevent an electrical hazard |
- MF
Specification | Objective |
---|---|
All mechanically-supplied outdoor air must pass through a filter before combining with conditioned air Filtration must meet a minimum efficiency of MERV 8 Filter or air cleaning systems that intentionally produce ozone are not allowed. |
Outdoor air filtered for particles |
- MF
Specification | Objective |
---|---|
Install filtration in a readily accessible location for service Filter opening must allow filter to be fully removed and inserted without bending or damaging the filter Filter access panel must include gasket or comparable sealing mechanism and fit snugly against exposed edge of filter when closed Filter plenum must be airtight and mechanically fastened to adjoining ductwork |
Filter accessible for service and prevents air bypass |
- MF
Specification | Objective |
---|---|
Mount fan using mechanical fasteners per manufacturer's specifications and applicable code (e.g., seismic restraints) Isolate air handling unit from the building framing unless specifically designed to be directly attached |
Secure, vibration-isolated air handler |
- MF
Specification | Objective |
---|---|
Attach ductwork to air handler via a flexible connection and that maintains the intended fan opening |
Efficient, vibration-resistant plenum connections |
- MF
Specification | Objective |
---|---|
Seal all air moving portions of the system using UL 181 products |
Airtight ventilation system |
- MF
Specification | Objective |
---|---|
Provide air flow by sequenced or scheduled operation of the damper or equivalent technology Control system must operate both the air handler and the motorized damper or be interlocked to prevent damper operation when air handler is not on |
Sufficient controlled ventilation rate |
- MF
Specification | Objective |
---|---|
Ensure motorized damper, service disconnect switch, fan, filter, and conditioning coils are accessible for maintenance according to NEC and applicable building code |
Serviceable parts are readily accessible |
- MF
Specification | Objective |
---|---|
If fire dampers are required in the fresh air supply duct, install them according to applicable building code Fire dampers must be accessible for inspection and/or testing Sealing activities must not interfere with the operation of fire dampers, balancing dampers, or backdraft dampers |
Fire dampers function effectively and are accessible |
- MF
Specification | Objective |
---|---|
Adjust fan speed, dampers, and registers until design specifications are met |
Ensure complete dwelling ventilation |