Durable, weather-proof, and effective, exterior thermal boundary
Specifications
- SF
- MF
Specification | Objective |
---|---|
Verify that installation area is free of: |
Ensure wall space can be safely and durably insulated |
- SF
- MF
Specification | Objective |
---|---|
Select panels in compliance with the AHJ, Select panel design that meets the fire-safety requirements of the AHJ Consider if challenging wall details might be resolved with the use of different retrofit panel thicknesses Determine if windows and doors should be relocated to newly created plane of retrofit wall system with built-out framing or left in place at current wall plane |
Prevent condensation on warm side of retrofit panel |
- SF
- MF
Specification | Objective |
---|---|
Remove all exterior cladding from the installation area Seal all holes, gaps, and penetrations in existing sheathing airtight Remove any existing insulation or protrusions that prevent full insulation contact with existing air barrier Replace any rotten or structurally weak substrate |
Provide secure attachment surface for insulation panels to existing exterior sheathing |
- SF
- MF
Specification | Objective |
---|---|
Install panels to prescribed R-value in compliance with the manufacturer's instructions including: using fasteners of the proper length and material, installing fasteners with correct fastener spacing, and Install panels above grade as per manufacture's specification Seal all insulation seams, joints and connections in each layer with compatible sealant (caulk, tape, mastic, etc.) |
Select safe and effective fasteners and sealants that provide secure and weathertight contact with retrofit panels to existing sheathing |
- SF
- MF
Specification | Objective |
---|---|
Make windows, doors, and other penetrations weather-tight Verify intentional drainage is functioning correctly (do not seal drainage weep holes) Verify safe operation of windows and doors Install finish siding according to manufacturer’s specification |
Maintain drainage plane while ensuring proper operation of fenestration |
- SF
- MF
Specification | Objective |
---|---|
Ensure that insulation retrofit complies with applicable code regarding fire safety |
- SF
- MF
Specification | Objective |
---|---|
Post a dated statement signed by the installer that minimally includes: Installed insulation type, coverage area, installed thickness, and installed R-value |
Comply with 16 CFR 460.17 and document contract compliance |