Continuous, contiguous, safe, compliant, and pest-resistant thermal barrier
Specifications
- MH
Specification | Objective |
---|---|
Verify that installation area is free of: active water leaks, fuel leaks (i.e., gas, oil, propane), and pest intrusions uncovered electrical junctions improperly terminated devices (ventilation fans, dryers, plumbing stacks, condensate lines, combustion appliance flues/chimneys, etc.) unshielded high-temperature devices (non-IC rated recessed lights, chimneys, flues, vents, etc.) unless they are zero clearance devices insulation escape openings Verify that installation area: is intact, able to support insulation weight, and air sealed |
Ensure space can be safely insulated |
- MH
Specification | Objective |
---|---|
Create access to attic by removing existing gable vents or installing new gable vents on each gable of the home that are large enough for access to install insulation correctly |
Access entire cavity through gable vents |
- MH
Specification | Objective |
---|---|
Fill entire attic to prescribed R-value If existing insulation is roof-mounted, insulation will be blown below If existing insulation is ceiling-mounted, insulation will be blown above If existing insulation is mounted at both locations, insulation will be blown in between |
Continuous thermal barrier of consistent R-value |
- MH
Specification | Objective |
---|---|
Install gable vents using mechanical fasteners ensuring vents are oriented per the manufacturer's specifications Install gable vents with a pest intrusion screening with a maximum hole size of 1/2" |
Weatherproof and pest-resistant gable access closure |
- MH
Specification | Objective |
---|---|
Post a dated receipt signed by the installer that minimally includes: Installed insulation type, coverage area, installed thickness, minimum settled thickness, installed R-value, and number of bags installed |
Comply with 16 CFR 460.17 and document contract compliance |