SPF in Open Joisted Cavities

Detail ID 4.0301.5
Topic
Floors
Subtopic
Accessible Floors
Desired Outcome

Continuous, contiguous, and safe thermal boundary that prevents air movement @ 50 Pascals

SF Single Family Site-Built Housing
MH Manufactured Housing
MF Multifamily Housing

Specifications

  • SF
  • MH
  • MF
Specification Objective

Verify that installation area is free of:

active water leaks, fuel leaks (i.e., gas, oil, propane), and pest intrusions

energized or undammed knob and tube wiring

uncovered electrical junctions

improperly terminated devices (ventilation fans, dryers, plumbing stacks, condensate lines, combustion appliance flues/chimneys, etc.)

unshielded high-temperature devices (non-IC rated recessed lights, chimneys, flues, vents, etc.) unless they are zero clearance devices

insulation escape openings

Verify that installation area is:

intact, able to support insulation weight, and air sealed

Ensure insulation can be safely installed

  • SF
  • MH
  • MF
Specification Objective

Select insulation that has a flame spread and smoke development index of 75/450 or less when tested in accordance with ASTM E84 or UL 723

Select fire safe materials

  • SF
  • MH
  • MF
Specification Objective

Prepare the surface according to manufacturer's specifications

Install durable backing material over any escape holes in the air barrier

Install flags that can be seen below the floor joists at all utility junctions for future identification and ensure utility junctions remain accessible per local code requirements

Prevent SPF leakage, identify utility junctions for future access

  • SF
  • MH
  • MF
Specification Objective

Remove contaminants from all SPF application surfaces that will prevent full adhesion or cause degradation

Verify all SPF application surfaces are in accordance with manufacturer specifications for moisture content and temperature

Properly bonded SPF installation

  • SF
  • MH
  • MF
Specification Objective

Apply SPF to prescribed R-value over bottom of subfloor, and all surfaces of the floor joists (including the bottom), using a pass thickness maximum as indicated by manufacturer specifications

Install to a thickness of least a class I vapor retarder or have at least a class I vapor retarder coating or covering in direct contact with the underside of the SPF

Continuous pressure and thermal boundary that prevents moisture vapor movement

  • SF
  • MH
  • MF
Specification Objective

Separate all foam products from living space with a thermal barrier material (e.g., 1/2" gypsum wallboard) as specified by applicable building code

If space is used only for the service of utilities, foam will be separated from the space using a suitable ignition barrier covering or coating according to manufacturer's specifications

If space is used for storage or occupancy, spray foam will be separated from the space using a thermal barrier material (e.g., 1/2" gypsum wallboard) as specified by applicable building code and manufacturer specifications

If code requirements are unclear, consult local code officials for clarification

Minimize ignition and combustion potential

  • SF
  • MH
  • MF
Specification Objective

Post a dated receipt signed by the installer that minimally includes: Installed insulation type, coverage area, installed thickness, and installed R-value

Comply with 16 CFR 460.17 and document contract compliance