Cantilever Floor Joisted Cavities Batt Insulation

Detail ID 4.0301.6
Topic
Floors
Subtopic
Accessible Floors
Desired Outcome

Continuous, contiguous, and safe thermal boundary that prevents air movement @ 50 Pascals

SF Single Family Site-Built Housing
MH Manufactured Housing
MF Multifamily Housing

Specifications

  • SF
  • MH
  • MF
Specification Objective

Verify that installation area is free of:

active water leaks, fuel leaks (i.e., gas, oil, propane), and pest intrusions

energized knob and tube wiring

uncovered electrical junctions

improperly terminated devices (ventilation fans, dryers, plumbing stacks, condensate lines, combustion appliance flues/chimneys, etc.)

unshielded high-temperature devices (non-IC rated recessed lights, chimneys, flues, vents, etc.) unless they are zero clearance devices

insulation escape openings

Verify that installation area is:

intact, able to support insulation weight, and air sealed

Ensure space can be safely insulated

  • SF
  • MH
  • MF
Specification Objective

Select insulation that has a flame spread and smoke development index of 25/450 or less when tested in accordance with ASTM E84 or UL 723

Select fire safe materials

  • SF
  • MH
  • MF
Specification Objective

Remove any existing insulation or vapor barrier materials from installation area

Install airtight blocking between each floor joist at the interior edge of the exterior wall plate

Prevent condensation, prevent air and moisture movement in attached floor cavities

  • SF
  • MH
  • MF
Specification Objective

Install batt insulation to prescribed R-value in every joist bay in full contact with the air barrier and all sides of the cavity without gaps, voids, compressions, or misalignments

If batt contains a facing material install it in contact with the conditioned space

Continuous and contiguous thermal boundary

  • SF
  • MH
  • MF
Specification Objective

Secure batts in full contact with the pressure boundary using physical fasteners that do not compress the insulation and have a minimum service life of 20 years (e.g., strapping, netting, wood strips)

Insulation remains in contact with pressure boundary

  • SF
  • MH
  • MF
Specification Objective

Mechanically fasten a continuous, airtight, rigid air barrier to underside of floor assembly that is suitable to withstand weather, moisture, and pest contact

Weathertight, pest resistant, rigid enclosure

  • SF
  • MH
  • MF
Specification Objective

Install durable exterior soffit material over the rigid enclosure materials

Protect enclosed cavity from weather

  • SF
  • MH
  • MF
Specification Objective

Post a dated receipt signed by the installer that minimally includes: Installed insulation type, coverage area, installed thickness, and installed R-value

Comply with 16 CFR 460.17 and document contract compliance