Continuous, contiguous, and safe thermal boundary that prevents air movement @ 50 Pascals
Specifications
- SF
- MF
Specification | Objective |
---|---|
Verify that installation area is free of: active water leaks, fuel leaks (i.e., gas, oil, propane), and pest intrusions energized knob and tube wiring uncovered electrical junctions improperly terminated devices (ventilation fans, dryers, plumbing stacks, condensate lines, combustion appliance flues/chimneys, etc.) unshielded high-temperature devices (non-IC rated recessed lights, chimneys, flues, vents, etc.) unless they are zero clearance devices insulation escape openings Verify that installation area is: intact, able to support insulation weight, and air sealed |
Ensure space can be safely insulated |
- SF
- MF
Specification | Objective |
---|---|
Select batt insulation that has a class II vapor retarder facing and that has a flame spread and smoke development index of 25/450 or less Select encapsulation material that is a permanent air barrier, a class II vapor retarder, and has a smoke development index of 450 or less when tested in accordance with ASTM E84 or UL 723 |
Select materials that are fire safe and meet class II vapor retarder requirement |
- SF
- MF
Specification | Objective |
---|---|
Select sealants that: are compatible with their intended surfaces allow for differential expansion and contraction between dissimilar materials meet the requirements of the applicable fire safety code (e.g., thermal or ignition barriers) |
Select safe and effective sealants |
- SF
- MF
Specification | Objective |
---|---|
Remove any existing insulation or vapor barrier materials from installation area |
Prevent condensation, align thermal and pressure boundary |
- SF
- MF
Specification | Objective |
---|---|
Install batt insulation to prescribed R-value in every joist bay in full contact with the rim/band joist air barrier and all sides of the cavity without gaps, voids, compressions, or misalignments If batt contains a facing material install it toward the conditioned space |
Continuous and contiguous thermal boundary |
- SF
- MF
Specification | Objective |
---|---|
Seal each cavity airtight around the perimeter of faced batts or around the perimeter of the encapsulation material |
Prevent air and moisture movement in cavity |
- SF
- MF
Specification | Objective |
---|---|
Post a dated receipt signed by the installer that minimally includes: Installed insulation type, coverage area, installed thickness, and installed R-value |
Comply with 16 CFR 460.17 and document contract compliance |