Remove appliance condensation from building and prevent damage to structure
Specifications
- SF
- MH
- MF
Specification | Objective |
---|---|
Convey all condensate from all cooling coils, condensing furnaces, etc. to the exterior of the building Condensate from condensing furnaces must first pass through a neutralizer if using waste lines for disposal |
Condensate safely drained to exterior |
- SF
- MH
- MF
Specification | Objective |
---|---|
Seal all piping that conveys condensate |
Leak free condensate piping |
- SF
- MH
- MF
Specification | Objective |
---|---|
Install condensate piping with not less than 1/8" per foot (1% slope) towards the termination point |
Condensate drains toward termination |
- SF
- MH
- MF
Specification | Objective |
---|---|
Install vents and traps on condensate drain lines in accordance with manufacturer specifications and applicable building code and in a manner that allows for cleaning of condensate lines without cutting the existing pipe |
Condensate drain operates as intended |
- SF
- MH
- MF
Specification | Objective |
---|---|
Install a secondary drain pan under all condensing appliances installed in or above conditioned space and where water damage may occur to the structure Install an independent condensate drain for the secondary drain pan that drains to a visible termination location Slope drain pan towards the condensate drain |
Prevent water damage to dwelling |
- SF
- MH
- MF
Specification | Objective |
---|---|
Install a float switch in the primary and secondary drain pan that is interlocked with the system power circuit and will break the circuit when drainage fails to remove condensate |
Stop system operation if condensate is not draining |
- SF
- MH
- MF
Specification | Objective |
---|---|
When there is potential for condensation or freezing of the drain line, insulate condensate drain lines to a minimum of R-4 with insulation that contains a Class II or greater vapor retarder |
Prevent freezing and condensation on pipes |
- SF
- MH
- MF
Specification | Objective |
---|---|
Install condensate drain pumps when condensate cannot be drained by gravity |
Convey condensate to exterior without gravity assistance |
- SF
- MH
- MF
Specification | Objective |
---|---|
If termination of condensate drain is to the outdoors, direct it downwards with an elbow fitting at the end of the exterior termination |
Condensate drains to exterior and away from building |