Emergency Lighting Replacement

Detail ID 7.0103.5
Topic
Plug Load
Subtopic
Lighting
Desired Outcome

Safe, efficient, and compliant emergency lighting replacement

SF Single Family Site-Built Housing
MH Manufactured Housing
MF Multifamily Housing

Specifications

  • MF
Specification Objective

Select emergency light fixtures that:

are UL approved for location installed (i.e., indoor, outdoor, wet location)

have battery-backup that can maintain the total load for a minimum period of 1-1/2 hours, in accordance with section 700.12 of the NEC

Select efficient, reliable, and safe lighting improvements

  • MF
Specification Objective

De-energize circuit and lock out power before work begins

Locate and install fixture in accordance with NFPA 101 and NFPA 70 and as specified by NECA/IESNA 500

Safe, proper, and functioning installation

  • MF
Specification Objective

Permanently remove equipment from job site and recycle or dispose of removed equipment and refrigerant in accordance with local and federal law (e.g., EPA Section 608 of Clean Air Act of 1990)

Permanently decommission old equipment

Old equipment is permanently removed from service, protect the environment, and comply with regulation

  • MF
Specification Objective

Provide occupants/owners with user's manual, warranty information, installation instructions, and installer contact information

Manufacturer supplied information available to occupant